Legacyt RNC Line Air Conditioners
with Puronr Refrigerant
1--1/2 To 5 Nominal Tons
Installation Instructions
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency must use factory--authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Use quenching cloth for brazing operations.
Have fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions included in
literature and attached to the unit. Consult local building codes and
current editions of the National Electrical Code ( NEC ) NFPA 70.
In Canada, refer to current editions of the Canadian electrical code
CSA 22.1.
Recognize safety information. This is the safety--alert symbol
!
!
When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury. Understand
these signal words; DANGER, WARNING, and CAUTION. These
words are used with the safety--alert symbol. DANGER identifies
the most serious hazards which will result in severe personal injury
or death. WARNING signifies hazards which could result in
personal injury or death. CAUTION is used to identify unsafe
practices which would result in minor personal injury or product
and property damage. NOTE is used to highlight suggestions
which will result in enhanced installation, reliability, or operation.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF position.
There may be more than 1 disconnect switch. Lock out and
tag switch with a suitable warning label.
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and
wear appropriate protective clothing and gloves when
handling parts.
CAUTION
!
GENERAL
NOTE: In some cases noise in the living area has been traced to
gas pulsations from improper installation of equipment.
1. Locate unit away from windows, patios, decks, etc. where
unit operation sound may disturb customer.
2. Ensure that vapor and liquid tube diameters are appropriate
for unit capacity.
3. Run refrigerant tubes as directly as possible by avoiding un-
necessary turns and bends.
4. Leave some slack between structure and unit to absorb vi-
bration.
5. When passing refrigerant tubes through the wall, seal open-
ing with RTV or other pliable silicon--based caulk. (See Fig.
1.)
6. Avoid direct tubing contact with water pipes, duct work,
floor joists, wall studs, floors, and walls.
7. Do not suspend refrigerant tubing from joists and studs with
a rigid wire or strap which comes in direct contact with
tubing.(See Fig. 1.)
8. Ensure that tubing insulation is pliable and completely sur-
rounds vapor tube.
9. When necessary, use hanger straps which are 1 in. (25.4
mm) wide and conform to shape of tubing insulation. (See
Fig. 1.)
10. Isolate hanger straps from insulation by using metal sleeves
bent to conform to shape of insulation.
INSULATION
VAPOR TUBE
LIQUID TUBE
OUTDOOR WALL
INDOOR WALL
LIQUID TUBE
VAPOR TUBE
INSULATION
CAULK
Avoid contact between tubing and structureNOTE:
THROUGH THE WALL
HANGER STRAP
(AROUND VAPOR
TUBE ONLY)
JOIST
1” (25.4 mm) MIN.
SUSPENSION
A94026
Fig. 1 -- Piping Installation
Przeglądanie stron 0
1 2 3 4 5 6 7 8 9 10

Podsumowanie treści

Strona 1 - Installation Instructions

113A, 116BLegacyt RNC Line Air Conditionerswith Puronr Refrigerant1--1/2 To 5 Nominal TonsInstallation InstructionsSAFETY CONSIDERATIONSImproper insta

Strona 2 - INSTALLATION

10PURONR (R--410A) REFRIGERANT QUICK REFERENCE GUIDES Puron refrigerant operates at 50--70 percent higher pressures than R--22. Be sure that servicing

Strona 3

2The outdoor unit contains system refrigerant charge for operationwith AHRI rated indoor unit when connected by 15 ft. (4.57 m) offield--supplied or f

Strona 4 - 113A / 116B

3Outdoor Unit Connected to Factory Approved IndoorUnitOutdoor unit contains correct system refrigerant charge foroperation with factory approved AHRI

Strona 5

4Installing with Indoor PistonOutdoor Unit Connected to Factory Approved Indoor UnitCheck piston size shipped with indoor unit to see if it matchesreq

Strona 6

5Table 2 – Rating Plate (required) Subcooling TemperaturesMeasureLiquid Pressure(psig)R --- 410A Required Liquid Line Temperature _F(_C)_F (_C) _F (_C

Strona 7 - Start--Up

6Table 4 – Required Suction--Line TemperatureSUPERHEAT TEMP (_F)SUCTION PRESSURE AT SERVICE PORT (PSIG)107.8 112.2 116.8 121.2 126 130.8 138.8 140.8 1

Strona 8 - CARE AND MAINTENANCE

7Make Electrical ConnectionsBe sure field wiring complies with local and national fire, safety,and electrical codes, and voltage to system is within l

Strona 9

83--Phase MonitorIn 3--phase units a small circuit board is factory installed to monitorline voltage. A small led will flash if a phase problem exists

Strona 10 - ---116B---07

9Table 6 – Accessory UsageACCESSORYREQUIRED FOR LOW--- AMBIENTCOOLING APPLICATIONS(Below 55°F/12.8_C)REQUIRED FOR LONG LINEAPPLICATIONS*REQUIRED FORSE