Form No. PDS548F-36-6
COMMERCIAL
SINGLE PACKAGE ROOFTOP
STANDARD AND HIGH EFFICIENCY
HEAT PUMP UNITS
Standard-Efficiency (548F), and High-Efficiency (549B, 549C,
542J) heat pump units offer:
• Pre-painted galvanized steel cabinet for long life and quality
appearance
• Commercial strength base rails with built-in rigging capability
• Convertible design for vertical or horizontal supply/return
• Non-corrosive, sloped condensate drain pan, meets
ASHRAE 62 (IAQ)
• Two-inch return-air filters
• A wide assortment of factory-installed options available,
including high-static drives that provide additional perfor-
mance range
• Factory-installed optional gear driven EconoMi$erIV (vertical
return for sizes 024-120 only) for use with standard rooftop
unit controls (includes CO
2
sensor control capability)
• Factory-installed optional gear driven EconoMi$er2 (vertical
return only) for use with third party controls (includes 4 to
20 mA actuator for demand control ventilation)
• State-of-the-art defrost system
• Dependable 4-way valve operation
Heat Options
• Field-installed electric heat available
• Glycol hydronic coils
FEATURES/BENEFITS
Every compact one-piece unit arrives fully assembled,
charged, tested, and ready to run.
QUIET, EFFICIENT OPERATION AND DEPENDABLE PER-
FORMANCE — Compressors have vibration isolators for quiet
operation. Efficient fan and motor design permits operation at
low sound levels.
Unit sizes 090-180 offer lower utility costs through part-load
operation using 2 stages of cooling.
Quiet and efficient operation is provided by belt-driven indoor
fans (standard on all units over 5 tons). The belt-driven indoor
fan is equipped with variable-pitch pulleys which allow adjust-
ment within the rpm ranges of the factory-supplied pulleys.
Increased operating efficiency is achieved through computer-
designed coils featuring staggered internally enhanced copper
tubes. Fins are ripple-edged for strength, lanced, and double
waved for higher heat transfer.
Models 542J, 548F, 549B, 549C
Sizes 024-180
DuraPac and DuraPac Plus
2 to 15 Tons
548F036-072
549B036-072
549C024-060
548F090-120
549B090-120
542J150,180
50-1219
50-1304
50-1214
Przeglądanie stron 0
1 2 3 4 5 6 ... 169 170

Podsumowanie treści

Strona 1 - Models 542J, 548F, 549B, 549C

Form No. PDS548F-36-6COMMERCIALSINGLE PACKAGE ROOFTOPSTANDARD AND HIGH EFFICIENCYHEAT PUMP UNITSStandard-Efficiency (548F), and High-Efficiency (549B,

Strona 2 - TABLE OF CONTENTS

10OPTIONS AND ACCESSORIES (cont)Roof Curbs (Horizontal and Vertical) permit installation andsecuring of ductwork to curb prior to mounting unit on the

Strona 3

100PERFORMANCE DATA — 549B, 549C (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 840 to 1085 rpm. All other rpms requ

Strona 4 - Quality Assurance

101PERFORMANCE DATA — 549B, 549C (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 860 to 1080 rpm. All other rpms requ

Strona 5

102PERFORMANCE DATA — 549B, 549C (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 860 to 1080 rpm. All other rpms requ

Strona 6 - ARI* CAPACITY RATINGS (cont)

103PERFORMANCE DATA — 549B, 549C (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 922 to 1219 rpm. All other rpms requ

Strona 7 - OPTIONS AND ACCESSORIES

104PERFORMANCE DATA — 549B, 549C (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS LEGEND*Motor drive range: 639 to 936 rpm.

Strona 8 - 549B036-120, 549C024-060

105PERFORMANCE DATA — 549B, 549C (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 770 to 1185 rpm. All other rpms re

Strona 9

106PERFORMANCE DATA — 549B, 549C (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 1035 to 1460 rpm. All other rpms r

Strona 10

107PERFORMANCE DATA — 549B, 549C (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 1300 to 1685 rpm. All other rpms r

Strona 11

108PERFORMANCE DATA — 549B, 549C (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 1300 to 1685 rpm. All other rpms r

Strona 12

109PERFORMANCE DATA — 549B, 549C (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 730 to 950 rpm. All other rpms req

Strona 13 - FILTER HINGED PANEL OPTION

11OPTIONS AND ACCESSORIES (cont)TR124 VacCOMTR24 VacHOT12345EFEF1+_P1T1PTNEXH2V 10VEXHSetSet2V 10V2V 10VDCVDCVFreeCoolBCADSO+SR+SRSOAQ1AQDCVMinPosOpen

Strona 14 - PHYSICAL DATA

110PERFORMANCE DATA — 549B, 549C (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 860 to 1080 rpm. All other rpms re

Strona 15

111PERFORMANCE DATA — 549B, 549C (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 840 to 1085 rpm. All other rpms re

Strona 16

112PERFORMANCE DATA — 549B, 549C (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 860 to 1080 rpm. All other rpms re

Strona 17 - BASE UNIT DIMENSIONS (cont)

113PERFORMANCE DATA — 549B, 549C (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 860 to 1080 rpm. All other rpms re

Strona 18 - ACCESSORY DIMENSIONS

114PERFORMANCE DATA — 549B, 549C (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 922 to 1219 rpm. All other rpms re

Strona 19 - ACCESSORY DIMENSIONS (cont)

115PERFORMANCE DATA — 549B, 549C (cont)FAN RPM AT MOTOR PULLEY SETTINGS**Approximate fan rpm shown.†Indicates standard motor and drive package.**Indic

Strona 20

116PERFORMANCE DATA — 549B, 549C (cont)ACCESSORY ELECTRIC HEATERS STATIC PRESSURE* (in. wg) — 549B036-072 AND 549C024-060 LEGEND*The s

Strona 21 - PERFORMANCE DATA — 548F

117PERFORMANCE DATA — 549B, 549C (cont)ELECTRIC HEATING CAPACITIES — 549B036-120 AND 549C024-060*Two heater packages required to provide kW indicated.

Strona 22 - COOLING CAPACITIES (cont)

118PERFORMANCE DATA — 549B, 549C (cont)ELECTRIC HEATING CAPACITIES — 549B036-120 AND 549C024-060 (cont)*Two heater packages required to provide kW ind

Strona 23

119ELECTRICAL DATA — 549B549B036-120 STANDARD MOTOR UNITS WITHOUT ELECTRICAL CONVENIENCE OUTLETSee Legend on page 114.UNIT549BNOMINALVOLTAGEV-PH-HzVOL

Strona 24

12OPTIONS AND ACCESSORIES (cont)CONTROL BOX HINGED PANEL OPTION, 549B036-072 UNITS SHOWNCONTROL BOX HINGED PANEL OPTION, 549B090-120 UNITS SHOWNCOMPRE

Strona 25

120ELECTRICAL DATA — 549B (cont)549B036-120 STANDARD MOTOR UNITS WITHOUT ELECTRICAL CONVENIENCE OUTLET (cont) LEGEND*Heat

Strona 26

121ELECTRICAL DATA — 549B (cont)549B036-120 — STANDARD MOTOR UNITS WITH ELECTRICAL CONVENIENCE OUTLETSee Legend on page 122.UNIT549BNOMINALVOLTAGEV-PH

Strona 27 - GENERAL FAN PERFORMANCE NOTES

122ELECTRICAL DATA — 549B (cont)549B036-120 — STANDARD MOTOR UNITS WITH ELECTRICAL CONVENIENCE OUTLET (cont) LEGEND*Heate

Strona 28

123ELECTRICAL DATA — 549B (cont)549B036-120 — HIGH-STATIC MOTOR UNITS WITHOUT ELECTRICAL CONVENIENCE OUTLETSee Legend on page 124.UNIT549BNOMINALVOLTA

Strona 29

124ELECTRICAL DATA — 549B (cont)549B036-120 — HIGH-STATIC MOTOR UNITS WITHOUT ELECTRICAL CONVENIENCE OUTLET (cont) LEGEND

Strona 30

125ELECTRICAL DATA — 549B (cont)549B036-120 — HIGH-STATIC MOTOR UNITS WITH ELECTRICAL CONVENIENCE OUTLETSee Legend on page 126.UNIT549BNOMINALVOLTAGEV

Strona 31

126ELECTRICAL DATA — 549B (cont)549B036-120 — HIGH-STATIC MOTOR UNITS WITH ELECTRICAL CONVENIENCE OUTLET (cont) LEGEND*He

Strona 32

127ELECTRICAL DATA — 549C549C024-060 — STANDARD MOTOR UNITS WITHOUT ELECTRICAL CONVENIENCE OUTLETSee Legend on page 128.UNIT549CNOMINAL VOLTAGE (V-Ph-

Strona 33

128ELECTRICAL DATA — 549C (cont)549C024-060 — HIGH-STATIC MOTOR UNITS WITHOUT ELECTRICAL CONVENIENCE OUTLET LEGEND*Heate

Strona 34

129ELECTRICAL DATA — 549C (cont)549C024-060 — STANDARD MOTOR UNITS WITH ELECTRICAL CONVENIENCE OUTLETSee Legend on page 130.UNIT549CNOMINAL VOLTAGE (V

Strona 35

13OPTIONS AND ACCESSORIES (cont)EVAPORATOR-FAN HINGED PANEL OPTIONFILTER HINGED PANEL OPTIONNOTE: Hinged access panels are not available on 548F units

Strona 36

130ELECTRICAL DATA — 549C (cont)549C036-060 — HIGH-STATIC MOTOR UNITS WITH ELECTRICAL CONVENIENCE OUTLET LEGEND*Heater ca

Strona 37

131TYPICAL WIRING SCHEMATICS — 549B, 549CLEGENDAWG — American Wire GageC—Contactor, CompressorCAP — CapacitorCB — Circuit BreakerCLO — Compressor Lock

Strona 38

132TYPICAL WIRING SCHEMATICS — 549B, 549C (cont)EconoMi$erIV Wiring — 549B036-120, 549C024-060LEGENDIAQ — Indoor Air QualityLA — Low Ambient Lockout D

Strona 39

133TYPICAL WIRING SCHEMATICS — 549B, 549C (cont)C2 FOR 090-120 UNITSLINE SIDEC1113232321BLUBLUGRAGRAREDGRAREDREDYELYEL208-230-1 ONLY240VH1H1H3H2H2H4T

Strona 40

134TYPICAL PIPING AND WIRING — 549B036-120, 549C024-060Vertical Discharge DuctingHorizontal Discharge DuctingLEGENDNEC — National Electrical Code50-12

Strona 41

135GUIDE SPECIFICATIONS — 549B036-120, 549C024-060PACKAGED ROOFTOP AIR-TO-AIR HEAT PUMP —CONSTANT VOLUME APPLICATIONHVAC GUIDE SPECIFICATIONSSIZE RANG

Strona 42

136GUIDE SPECIFICATIONS — 549B036-120, 549C024-060 (cont)3. Coils:a. Copper-fin coils shall be constructed of copperfins mechanically bonded to copper

Strona 43

137GUIDE SPECIFICATIONS — 549B036-120, 549C024-060 (cont)3. Compressor with standard controls shall be capableof operation down to –20 F (in heating m

Strona 44

138GUIDE SPECIFICATIONS — 549B036-120, 549C024-060 (cont)* 5. 25% Two-Position Damper:a. Two-position damper package shall include singleblade damper

Strona 45

139GUIDE SPECIFICATIONS — 549B036-120, 549C024-060 (cont)23. Indoor Air Quality (CO2) Room Sensor(EconoMi$erIV):Sensor shall have the ability to provi

Strona 46

14PHYSICAL DATA548F036-072 LEGEND*Weight of 14-in. roof curb.†Single phase/three phase.NOTE: The 548F units have a loss-of-charge switch

Strona 47

140PHYSICAL DATA — 542J150,180 LEGEND*Weight of 14 in. roof curb.UNIT SIZE 542J150180203/230 V, 460 V 575 VNOMINAL CAPACITY (tons) 12.5 15OPERA

Strona 48

141BASE UNIT DIMENSIONS*Units with aluminum indoor and outdoor coil fins.UNIT542JMAXIMUM SHIPPING WEIGHT*lb kg150 1895 860180 2205 1000 LEGENDUNI

Strona 49

142ACCESSORY DIMENSIONS — 542J150,180PKG NO. REF.CURBHEIGHTDESCRIPTIONCRRFCURB010A00 1′-2″ (305) Standard Curb 14″ HighCRRFCURB011A00 2′-0″ (610)Stand

Strona 50

143ACCESSORY DIMENSIONS — 542J150,180 (cont)CONVENIENCEOUTLETFIELD POWER K.O.CONTROL POWER K.O.0’-4 1/2"(114)0’-7 3/16"(487)Horizontal Adapt

Strona 51

144ACCESSORY DIMENSIONS — 542J150,180 (cont)2'-1 5/8"2'-2 1/16"1'-6 5/16"Non-Fused Disconnect — 542J150,180Power Exhaust

Strona 52

145SELECTION PROCEDURE (WITH 542J180 EXAMPLE)I DETERMINE HEATING AND COOLING REQUIRE-MENTS AT DESIGN CONDITIONS:Given:Required Cooling Capacity (TC)

Strona 53

146PERFORMANCE DATA — 542JCOOLING CAPACITIESLEGENDNOTES:1. Direct interpolation is permissible. Do not extrapolate.2. The following formulas may be us

Strona 54

147PERFORMANCE DATA — 542J (cont)INTEGRATED HEATING CAPACITIES LEGENDNOTES:1. Integrated heating capacity ratings shown are not a

Strona 55 - ELECTRICAL DATA — 548F

148PERFORMANCE DATA — 542J (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS LEGEND*Standard drive range is 891 to 1179 rpm. Altern

Strona 56 - ELECTRICAL DATA — 548F (cont)

149PERFORMANCE DATA — 542J (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Standard drive range is 817 to 1038 rpm.

Strona 57

15PHYSICAL DATA548F090-120LEGENDBhp — Brake Horsepower*Weight of 14-in. roof curb.UNIT SIZE 548F 090 120NOMINAL CAPACITY (tons) 71/210OPERATING WEIGHT

Strona 58

150PERFORMANCE DATA — 542J (cont)FAN RPM AT MOTOR PULLEY SETTINGS**Approximate fan rpm shown.†Indicates standard motor and drive package.**Indicates s

Strona 59

151PERFORMANCE DATA — 542J (cont)ACCESSORY/FIOP STATIC PRESSURE* (in. wg) — 542J150,180 LEGEND*Units with electric heat are not des

Strona 60

152PERFORMANCE DATA — 542J (cont)GLYCOL COIL DATA* — 542J150,180 LEGEND *This accessory glycol coil is intended for use wi

Strona 61

153ELECTRICAL DATA — 542JELECTRICAL DATA — 542J150,180 LEGEND*Heater capacity (kW) is based on heater voltage of 208

Strona 62

154TYPICAL WIRING SCHEMATIC — 542J542J180 460 V Showna50-7581542J

Strona 63

155TYPICAL WIRING SCHEMATIC — 542J (cont)LEGENDC—Contactor, CompressorCAP — CapacitorCB — Circuit BreakerCH — Crankcase HeaterCLO — Compressor Lockout

Strona 64

156TYPICAL WIRING SCHEMATIC — 542J (cont)435286711011912PINKBLACKBLUENOTE 1NOTE 2RUN500 OHMRESISTOR50HJ540573ACTUATORASSEMBLYREDWHITEECONOMISER2 PLUGD

Strona 65 - 548F090-120 — 460 v Shown

157TYPICAL PIPING AND WIRING — 542J150,180LEGENDNOTES:1. Illustration shown is a general guide only and is not intended to include all details for any

Strona 66 - EconoMi$er2 Wiring

158GUIDE SPECIFICATIONS — 542J150,180PACKAGED ROOFTOP AIR-TO-AIR HEAT PUMP —CONSTANT VOLUME APPLICATIONHVAC GUIDE SPECIFICATIONSSIZE RANGE: 13 AND 15

Strona 67 - RED YEL BLU GRA

159GUIDE SPECIFICATIONS — 542J150,180 (cont)E. Coils:1. Standard indoor and outdoor coils shall have copperor aluminum plate fins mechanically bonded

Strona 68

16BASE UNIT DIMENSIONS548F036-072a50-8044548F

Strona 69

160GUIDE SPECIFICATIONS — 542J150,180 (cont)J. Operating Characteristics:1. Unit shall be capable of starting and running at 125 Fambient outdoor temp

Strona 70

161GUIDE SPECIFICATIONS — 542J150,180 (cont)5. Manual Outdoor-Air Damper:Manual damper package shall consist of damper,birdscreen, and rainhood which

Strona 71

162GUIDE SPECIFICATIONS — 542J150,180 (cont)24. Glycol Coil:Coil shall be 2-row copper tube (1/2-in. OD) withaluminum plate fins (15 fins/in.) and 1.6

Strona 72

163CONTROLSSEQUENCE OF OPERATION — 548F036-120, 549B036-120,AND 549C024-060Cooling, Units Without Economizer — When thermostat callsfor cooling, termi

Strona 73 - PHYSICAL DATA — 549B036-072

164CONTROLS (cont)Continuous Air Circulation — Turn unit power on. Set systemcontrol at OFF position. Set fan switch at ON position. Theindoor-fan con

Strona 74 - PHYSICAL DATA — 549B090-120

165APPLICATION DATA1. OUTDOOR INSTALLATION — Units approved for outdoorinstallation only.2. DUCTWORK — Secure vertical discharge ductwork to roofcurb.

Strona 75 - PHYSICAL DATA — 549C024-060

166APPLICATION DATA (cont)CONDENSER COIL PROTECTION APPLICATIONSLEGEND*See “Selection Guide: Environmental Corrosion Protection” Catalog No. 811-217 f

Strona 76

167APPLICATION DATA (cont)IAQ sensors — EconoMi$erIV can be utilized with any IAQ(CO2) sensor that provides a 2 to 10 vdc output. The con-troller will

Strona 77

168Outside air enthalpy — EconoMi$erIV will be enabledbased on the outside air enthalpy curves as shown in theEconoMi$erIV Changeover diagram below. T

Strona 79

17BASE UNIT DIMENSIONS (cont)548F090,120a50-8045548F

Strona 80

Copyright 2009 Bryant Heating & Cooling Systems Printed in U.S.A. 4/09 Catalog No. PDS548F-36-6SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICEUNIT

Strona 81

18ACCESSORY DIMENSIONSTO ENSURE AIRTIGHT CONNECTION.PLACE UNIT AS CLOSE TO THISEND AS POSSIBLETO ENSURE AIRTIGHT CONNECTION.PLACE UNIT AS CLOSE TO THI

Strona 82 - PERFORMANCE DATA — 549B, 549C

19ACCESSORY DIMENSIONS (cont)TO ENSURE AN AIRTIGHT CONNECTION,PLACE UNIT ON CURB AS CLOSE TODUCT END AS POSSIBLE.TO ENSURE AN AIRTIGHT CONNECTION,PLAC

Strona 83

2TABLE OF CONTENTSFeatures/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3Model Number Nomenclature . . . . . . . . . .

Strona 84

20SELECTION PROCEDURE (WITH 548F048 EXAMPLE)I DETERMINE COOLING AND HEATING LOADS ATDESIGN CONDITIONS.Given:Required Cooling Capacity (TC). . . . . .

Strona 85

21PERFORMANCE DATA — 548FCOOLING CAPACITIES548F036 (3 TONS)Temp (F)OutdoorEntering Air(Edb)Indoor Entering Air — Cfm/BF900/0.10 1200/0.15 1500/0.21Ind

Strona 86

22PERFORMANCE DATA — 548F (cont)COOLING CAPACITIES (cont)548F072 (6 TONS)Temp (F)OutdoorEntering Air(Edb)Indoor Entering Air — Cfm/BF1800/0.10 2400/0.

Strona 87

23PERFORMANCE DATA — 548F (cont)COOLING CAPACITIES (cont)LEGENDNOTES:1. Direct interpolation is permissible. Do not extrapolate.2. The following formu

Strona 88

24PERFORMANCE DATA — 548F (cont)INSTANTANEOUS AND INTEGRATED HEATING RATINGS (cont) LEGEND NOTES:1. i

Strona 89

25PERFORMANCE DATA — 548F (cont)INSTANTANEOUS AND INTEGRATED HEATING RATINGS (cont) LEGEND NOTES:1. in

Strona 90

26PERFORMANCE DATA — 548F (cont)INSTANTANEOUS AND INTEGRATED HEATING RATINGS (cont) LEGEND NOTES:1. in

Strona 91

27PERFORMANCE DATA — 548F (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITSLEGEND See General Fan Performance notes below. LEGEN

Strona 92

28PERFORMANCE DATA — 548F (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 1075 to 1455 rpm. A

Strona 93

29PERFORMANCE DATA — 548F (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 770 to 1175 rpm. Al

Strona 94

3INTEGRATED ECONOMIZERS AND OUTDOOR-AIRDAMPERSAvailable as options or accessories, economizers and manualoutdoor-air dampers introduce outdoor air whi

Strona 95

30PERFORMANCE DATA — 548F (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGEND See General Fan Performance notes on page 27.

Strona 96

31PERFORMANCE DATA — 548F (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 1300 to 1685 rpm. A

Strona 97

32PERFORMANCE DATA — 548F (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 1300 to 1685 rpm. A

Strona 98

33PERFORMANCE DATA — 548F (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 590 to 840 rpm. All other rpms require fiel

Strona 99

34PERFORMANCE DATA — 548F (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 685 to 935 rpm. All other rpms require fiel

Strona 100 - 549B, 549C

35PERFORMANCE DATA — 548F (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 860 to 1080 rpm. All other rpms require fie

Strona 101

36PERFORMANCE DATA — 548F (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 685 to 935 rpm. All other rpms require fiel

Strona 102

37PERFORMANCE DATA — 548F (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 835 to 1085 rpm. All other rpms require fie

Strona 103

38PERFORMANCE DATA — 548F (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 830 to 1130 rpm. All other rpms require fie

Strona 104

39PERFORMANCE DATA — 548F (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITSLEGENDSee General Fan Performance notes on page 27.

Strona 105

4MODEL NUMBER NOMENCLATURE — 548F UNITS(ODS Model Number)MODEL NUMBER NOMENCLATURE — 549B AND 549C UNITS(ODS Model Number)Voltage DesignationE– 460-3-

Strona 106

40PERFORMANCE DATA — 548F (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)LEGEND See General Fan Performance notes on page 27.

Strona 107

41PERFORMANCE DATA — 548F (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 1075 to 1455 rpm.

Strona 108

42PERFORMANCE DATA — 548F (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 878 to 1192 rpm.

Strona 109

43PERFORMANCE DATA — 548F (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 1070 to 1460 rpm.

Strona 110

44PERFORMANCE DATA — 548F (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 590 to 840 rpm. All other rpms require fi

Strona 111

45PERFORMANCE DATA — 548F (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 685 to 935 rpm. All other rpms require fi

Strona 112

46PERFORMANCE DATA — 548F (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 860 to 1080 rpm. All other rpms require f

Strona 113

47PERFORMANCE DATA — 548F (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 685 to 935 rpm. All other rpms require fi

Strona 114

48PERFORMANCE DATA — 548F (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 835 to 1085 rpm. All other rpms require f

Strona 115

49PERFORMANCE DATA — 548F (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 830 to 1130 rpm. All other rpms require f

Strona 116 - COMPONENT

5MODEL NUMBER NOMENCLATURE — 542J150,180 UNITSARI* CAPACITY RATINGS548F036-060548F072-120LEGEND*Air Conditioning and Refrigeration Institute.†Applies

Strona 117

50PERFORMANCE DATA — 548F (cont)FAN RPM AT MOTOR PULLEY SETTINGS* — 548F036-120*Approximate fan rpm shown.†Indicates alternate motor and drive package

Strona 118 - MULTIPLICATION FACTORS

51PERFORMANCE DATA — 548F (cont)0510152025300.13 0.20 0.22 0.25 0.30 0.35 0.40 0.45 0.50 036 - 072 090 - 120STATIC

Strona 119 - ELECTRICAL DATA — 549B

52PERFORMANCE DATA — 548F (cont)ELECTRIC HEATING CAPACITIES — 548F036-072*Two heater packages required to provide kW indicated.†Use CRSINGLE004A00 for

Strona 120 - ELECTRICAL DATA — 549B (cont)

53PERFORMANCE DATA — 548F (cont)ELECTRIC HEATING CAPACITIES — 548F090-120*Two heater packages required to provide kW indicated.NOTES:1. The rated heat

Strona 121

54PERFORMANCE DATA — 548F (cont)INDOOR-FAN MOTOR PERFORMANCE — 548F036-120 UNITSLEGENDBHP — Brake Horsepower*Extensive motor and electrical testing on

Strona 122

55ELECTRICAL DATA — 548F548F036-120 (UNITS WITHOUT ELECTRICAL CONVENIENCE OUTLET)NOTE: Legend and Notes for Electrical Data are on page 57.UNIT548FNOM

Strona 123

56ELECTRICAL DATA — 548F (cont)548F036-120 (UNITS WITHOUT ELECTRICAL CONVENIENCE OUTLET) (cont)NOTE: Legend and Notes for Electrical Data are on page

Strona 124

57ELECTRICAL DATA — 548F (cont)548F036-120 (UNITS WITHOUT ELECTRICAL CONVENIENCE OUTLET) (cont)LEGEND*Heaters are field installed only.†Used to determ

Strona 125

58ELECTRICAL DATA — 548F (cont)548F036-120 (UNITS WITHOUT ELECTRICAL CONVENIENCE OUTLET) (cont)NOTE: Legend and Notes for Electrical Data are on page

Strona 126

59ELECTRICAL DATA — 548F (cont)548F036-120 (UNITS WITHOUT ELECTRICAL CONVENIENCE OUTLET) (cont)NOTE: Legend and Notes for Electrical Data are on page

Strona 127 - ELECTRICAL DATA — 549C

6ARI* CAPACITY RATINGS (cont)549C024-060549B036-060549B072-120LEGEND*Air Conditioning and Refrigeration Institute.†Applies only to units with capacity

Strona 128 - ELECTRICAL DATA — 549C (cont)

60ELECTRICAL DATA — 548F (cont)548F036-120 (UNITS WITH ELECTRICAL CONVENIENCE OUTLET)NOTE: Legend and Notes for Electrical Data are on page 62.UNIT548

Strona 129

61ELECTRICAL DATA — 548F (cont)548F036-120 (UNITS WITH ELECTRICAL CONVENIENCE OUTLET) (cont)NOTE: Legend and Notes for Electrical Data are on page 62.

Strona 130

62ELECTRICAL DATA — 548F (cont)548F036-120 (UNITS WITH ELECTRICAL CONVENIENCE OUTLET) (cont)LEGEND*Heaters are field installed only.†Used to determine

Strona 131 - 549B036 208/230 v Shown

63ELECTRICAL DATA — 548F (cont)548F036-120 (UNITS WITH ELECTRICAL CONVENIENCE OUTLET) (cont)NOTE: Legend and Notes for Electrical Data are on page 64.

Strona 132

64ELECTRICAL DATA — 548F (cont)548F036-120 (UNITS WITH ELECTRICAL CONVENIENCE OUTLET) (cont)LEGEND*Heaters are field installed only.†Used to determine

Strona 133

65TYPICAL WIRING SCHEMATICS — 548FAWG — American Wire GageC—Contactor, CompressorCAP — CapacitorCB — Circuit BreakerCH — Crankcase HeaterCOMP — Compre

Strona 134 - Horizontal Discharge Ducting

66TYPICAL WIRING SCHEMATICS — 548F (cont)EconoMi$erIV Wiring435286711011912PINKVIOLETBLACKBLUEYELLOWNOTE 1NOTE 2RUN500 OHMRESISTOR-+OPTIONAL COSENSOR

Strona 135

67TYPICAL WIRING SCHEMATICS — 548F (cont)C2 FOR 008-014 UNITSLINE SIDEC1113232321BLUBLUGRAGRAREDGRAREDREDYELYEL208-230-1 ONLY240VH1H1H3H2H2H4TRAN4TRA

Strona 136

68TYPICAL PIPING AND WIRING — 548FVertical Discharge DuctingHorizontal Discharge DuctingLEGENDNEC — National Electrical Code50-127950-1297548F

Strona 137

69GUIDE SPECIFICATIONS — 548F036-120PACKAGED ROOFTOP AIR-TO-AIR HEAT PUMP WITH ELECTRIC HEAT OPTION — CONSTANT VOLUME APPLICATIONHVAC GUIDE SPECIFICAT

Strona 138

7OPTIONS AND ACCESSORIES548F036-120*Factory-installed.†Field-installed.NOTES:1. Refer to unit guide specifications, price pages, or contact yourlocal

Strona 139

70GUIDE SPECIFICATIONS — 548F036-120 (cont)c. E-Coated copper-fin coils shall have a flexibleepoxy polymer coating uniformly applied to all coilsurfac

Strona 140 - PHYSICAL DATA — 542J150,180

71GUIDE SPECIFICATIONS — 548F036-120 (cont)f. EconoMi$erIV and EconoMi$er2 shall be equippedwith a barometric relief damper capable of relievingup to

Strona 141 - BASE UNIT DIMENSIONS

72GUIDE SPECIFICATIONS — 548F036-120 (cont)12. Power Exhaust Accessory for EconoMi$erIV orEconoMi$er2:Power exhaust shall be used in conjunction withE

Strona 142 - 542J150,180

73PHYSICAL DATA — 549B036-072 LEGEND*Single phase/three phase.UNIT SIZE 549B 036 048 060 072NOMINAL CAPACITY (tons) 3456OPERATING WEIGHT

Strona 143

74PHYSICAL DATA — 549B090-120LEGENDBASE UNIT 549B 090 102 120NOMINAL CAPACITY (tons) 71/281/210OPERATING WEIGHT (lb)Unit 870 1000 1000EconoMi$erIV 75

Strona 144 - Power Exhaust — 542J150,180

75PHYSICAL DATA — 549C024-060LEGEND*Single phase/three phase.UNIT SIZE 549C 024 036 048 060NOMINAL CAPACITY (tons) 23 4 5OPERATING WEIGHT (lb)Unit 550

Strona 145

76BASE UNIT DIMENSIONS549B036-072a50-8054549B, 549C

Strona 146 - PERFORMANCE DATA — 542J

77BASE UNIT DIMENSIONS (cont)549B, 549C549B090-120a50-8055

Strona 147 - INTEGRATED HEATING CAPACITIES

78BASE UNIT DIMENSIONS (cont)549B, 549C549C024-060a50-8097

Strona 148

79ACCESSORY DIMENSIONSROOF CURBACCESSORYA UNIT SIZECRRFCURB001A011′-2″[356]549B, 549C024-072CRRFCURB002A012′-0″[610]NOTES:1. Roof curb accessory is sh

Strona 149

8OPTIONS AND ACCESSORIES (cont)549B036-120, 549C024-060*Factory-installed.†Field-installed.NOTES:1. Refer to unit guide specifications, price pages, o

Strona 150

80ACCESSORY DIMENSIONS (cont)CONNECTORPKG. ACCY.BCD ALT DRAIN HOLEGAS POWER CONTROLACCESSORYPOWERCRBTMPWR001A012′-87/16″[827]1′-1015/16″[583]13/4″[44.

Strona 151

81SELECTION PROCEDURE (WITH 549B048 EXAMPLE)I DETERMINE COOLING AND HEATING REQUIRE-MENTS AT DESIGN CONDITIONS:Given:Required Cooling Capacity (TC) .

Strona 152

82PERFORMANCE DATA — 549B, 549CCOOLING CAPACITIES549B036 (3 Tons)Temp (F)OutdoorEntering Air(Edb)Indoor Entering Air — Cfm/BF900/0.12 1200/0.15 1500/0

Strona 153 - ELECTRICAL DATA — 542J

83PERFORMANCE DATA — 549B, 549C (cont)COOLING CAPACITIES (cont)549B072 (6 Tons)Temp (F)OutdoorEntering Air(Edb)Indoor Entering Air — Cfm/BF1800/0.06 2

Strona 154 - 542J180 460 V Shown

84PERFORMANCE DATA — 549B, 549C (cont)COOLING CAPACITIES (cont)LEGENDNOTES:1. Direct interpolation is permissible. Do not extrapolate.2. The following

Strona 155

85PERFORMANCE DATA — 549B, 549C (cont)COOLING CAPACITIES (cont)LEGENDNOTES:1. Direct interpolation is permissible. Do not extrapolate.2. The following

Strona 156

86PERFORMANCE DATA — 549B, 549C (cont)COOLING CAPACITIES (cont)LEGENDNOTES:1. Direct interpolation is permissible. Do not extrapolate.2. The following

Strona 157

87PERFORMANCE DATA — 549B, 549C (cont)INSTANTANEOUS AND INTEGRATED HEATING RATINGS LEGEND NOTES:1. ind

Strona 158

88PERFORMANCE DATA — 549B, 549C (cont)INSTANTANEOUS AND INTEGRATED HEATING RATINGS (cont) LEGEND NOTE

Strona 159

89PERFORMANCE DATA — 549B, 549C (cont)INSTANTANEOUS AND INTEGRATED HEATING RATINGS (cont) LEGEND NOTE

Strona 160

9OPTIONS AND ACCESSORIES (cont)542J150,180*Factory-installed.†Field-installed.NOTES:1. Refer to unit price pages or contact your local representative

Strona 161

90PERFORMANCE DATA — 549B, 549C (cont)INSTANTANEOUS AND INTEGRATED HEATING RATINGS (cont) LEGEND NOTE

Strona 162

91PERFORMANCE DATA — 549B, 549C (cont)INSTANTANEOUS AND INTEGRATED HEATING RATINGS (cont) LEGEND NOTE

Strona 163 - CONTROLS

92PERFORMANCE DATA — 549B, 549C (cont)INSTANTANEOUS AND INTEGRATED HEATING RATINGS (cont) LEGEND NOTE

Strona 164 - CONTROLS (cont)

93PERFORMANCE DATA — 549B, 549C (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 680 to 1044 rpm. All other rpms requi

Strona 165 - APPLICATION DATA

94PERFORMANCE DATA — 549B, 549C (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 770 to 1185 rpm. All other rpms requi

Strona 166 - APPLICATION DATA (cont)

95PERFORMANCE DATA — 549B, 549C (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 1035 to 1460 rpm. All other rpms req

Strona 167

96PERFORMANCE DATA — 549B, 549C (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 1300 to 1685 rpm. All other rpms requ

Strona 168

97PERFORMANCE DATA — 549B, 549C (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 1300 to 1685 rpm. All other rpms requ

Strona 169

98PERFORMANCE DATA — 549B, 549C (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 730 to 950 rpm. All other rpms requir

Strona 170

99PERFORMANCE DATA — 549B, 549C (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 860 to 1080 rpm. All other rpms requi