Bryant 548J Instrukcja Użytkownika

Przeglądaj online lub pobierz Instrukcja Użytkownika dla Pompy Bryant 548J. Bryant 548J User Manual Instrukcja obsługi

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 0
548J
SINGLE PACKAGE HEAT PUMP/ELECTRIC HEAT
NOMINAL 3 TO 8.5 TONS
WITH PURON
R
(R--410A) REFRIGERANT
Service and Maintenance Instructions
TABLE OF CONTENTS
SAFETY CONSIDERATIONS 1....................
UNIT ARRANGEMENT AND ACCESS 3...........
SUPPLY FAN (BLOWER) SECTION 4..............
HEAT PUMP REFRIGERATION SYSTEM 8.........
PURON
R
(R--410A) REFRIGERANT 13.............
COOLING CHARGING CHARTS 14................
CONVENIENCE OUTLETS 19....................
HEAT PUMP CONTROLS 20......................
PROTECTIVE CONTROLS 20.....................
COMMERCIAL DEFROST CONTROL 21...........
ELECTRIC HEATERS 24.........................
SMOKE DETECTORS 26.........................
RTU--MP CONTROL SYSTEM 33..................
ECONOMIZER SYSTEMS 47.....................
WIRING DIAGRAMS 56.........................
PRE--START-UP 58..............................
START-UP, GENERAL 58.........................
START-UP, RTU--MP CONTROL 59................
OPERATING SEQUENCE 62......................
FASTENER TORQUE VALUES 67.................
APPENDIX I. MODEL NUMBER SIGNIFICANCE 68...
APPENDIX II. PHYSICAL DATA 69................
APPENDIX III. FAN PERFORMANCE 71...........
APPENDIX IV. ELECTRICAL INFORMATION 82....
APPENDIX V. WIRING DIAGRAM LIST 96.........
APPENDIX VI. MOTORMASTER SENSOR
LOCATIONS 97.................................
UNIT START-UP CHECKLIST 99..................
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment
can be hazardous due to system pressure and electrical
compone nts. Only trained and qualified service personnel
should install, repair, or service air-conditioning
equipment. Untrained personnel can perform the basic
maintenance functions of replacing filters. Trained service
personnel should perform all other operations.
When working on air-conditioni ng equipment, observe
precautions in the literature, tags and labels attached to
the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations.
Have fire extinguishers available for all brazing
operations.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for brazing operations. Have
fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions attached to
the unit. Consult local building codes and National
Electrical Code (NEC) for special requirements.
Recognize safety information. This i s the safety--alert
symbol
. When you see this symbol on the unit a nd in
instructions or manuals, be alert to the potential for
personal injury.
Understand the s ignal words DANGER, WARNING, and
CAUTION. These words are used with the safety--alert
symbol. DANGER identifies the most serious hazards
which will result in severe personal injury or death.
WARNING signifies a hazard which could result in
personal injury or death. CAUTION is used to identify
unsafe practices which may result in minor personal
injury or product and property damage. NOTE is used to
highlight suggestions which will result in enhanced
installation, reliability, or operation.
Przeglądanie stron 0
1 2 3 4 5 6 ... 99 100

Podsumowanie treści

Strona 1

548JSINGLE PACKAGE HEAT PUMP/ELECTRIC HEATNOMINAL 3 TO 8.5 TONSWITH PURONR(R--410A) REFRIGERANTService and Maintenance InstructionsTABLE OF CONTENTSSA

Strona 2

10Avoid sprayin g in horizontal pattern to minimize poten-tial for fin damage.7. Ensure cleaner thoroughly penetrates deep into fi nnedareas.8. Interi

Strona 3 - UNIT ARRANGEMENT AND ACCESS

100Manufacturer r es er ves the right to disc ontinue, or change at any time, specifications or designs without notice and without incurr ing obligati

Strona 4 - SUPPLY FAN (BLOWER) SECTION

11To EvaporatorCoilCircuitsFromLiquidHeaderMeteringOrificeC09229Fig. 15 -- Heat Pump Acutrol — Flow as EvaporatorFunctionConverging circuit flow in th

Strona 5 - 208/230-v Units

12Table 5 – Defrost Mode04A---07A and 08D--- 09D/Circuit 2:ComponentStatus/PositionDefrost Thermostat ClosedOutdoor Fan(s) OffReversin g Valve Energiz

Strona 6 - Supply Fan (Belt--Drive)

13PURONR(R--410A) REFRIGERANTThis unit is designed for use wit h Puron (R--410A)refrigerant. Do not use any other refrigerant i n thissystem.Puron (R-

Strona 7

14COOLING CHARGING CHARTSC09184Fig. 20 -- Cooling Charging Charts-- 548J*04AC09185Fig. 20 (cont.) -- Cooling Charging Charts -- 548J*05A548J

Strona 8 - HEAT PUMP REFRIGERATION

15C09186Fig. 20 (cont.) -- Cooling Charging Charts -- 548J*06AC09187Fig. 20 (cont.) -- Cooling Charging Charts -- 548J*07A548J

Strona 9

16C09188Fig. 20 (cont.) -- Cooling Charging Charts -- 548J*08DC09189Fig. 20 (cont.) -- Cooling Charging Charts -- 548J*09D548J

Strona 10 - Indoor Coil

17Compressor RotationPERSONAL INJURY HAZARDFailure to follow this caution may result in personalinjury.CAUTION!On 3--phase units with scroll compresso

Strona 11

18Table 6 – Heating and Cooling TroubleshootingPROBLEM CAUSE REMEDYCompressor andOutdoor FanWill Not Start.Power failure. Call power company.Fuse blow

Strona 12 - (Part No. EC39EZ067)

19CONVENIENCE OUTLETSELECTRICAL OPERATION HAZARDFailure to follow this warning could result in personalinjury or death.Units with conveni ence outlet

Strona 13 - (R--410A) REFRIGERANT

2ELECTRICAL OPERATION HAZARDFailure to follow this warning could result in personalinjury or death.Before performing service or maintena nce operation

Strona 14 - COOLING CHARGING CHARTS

20if the GFCI receptacle does not trip as required. Press theRESET button to clear the tripped condition.CO8283UNITVOLTAGECONNECTASPRIMARYCONNECTIONST

Strona 15

21OvertemperatureThe compressor has an internal protector to protect itagai nst excessively high discharge gas temperatures.High PressureSwitchThe sys

Strona 16

22C09276Fig. 27 -- Defrost Control Board (DFB) LocationTable 9 – 548J Defrost Board I/O and Jumper ConfigurationsInputsPoint Name Type of I/O Conne ct

Strona 17 - 0.14 in + 0.0 / -0.03

23Auxiliary (Electric) Heat control — The 548J unit can beequipped with one or two auxiliary electric heaters, toprovide a second stage of Heating. Th

Strona 18

24Shorting the jumpers for a period of 5 to 20 secs bypassesthe remaining continuous run period and places the unit ina Forced Defrost mode. If the co

Strona 19

25Single Point Boxes and Supplementary Fuses — Whenthe unit MOCP device value exceeds 60--A, unit--mountedsupplementary fuses are required for each he

Strona 20 - PROTECTIVE CONTROLS

26SMOKE DETECTORSSmoke detectors are available as factory--installed optionson 548J models. Smoke detectors may be specified forSupply Air onl y or fo

Strona 21 - COMMERCIAL DEFROST CONTROL

27such as smoke from a fire, causes the sensor to signal analarm state but dust and debris accumulated over timedoes not.For installations using two s

Strona 22

286. For units with an economizer, the sampling tube is in-tegra ted into the economizer housing but the conne c-tion of the flexible tubing to the sa

Strona 23 - 90 minutes

29Sensor and Controller TestsSensor Alarm TestThe sensor alarm test checks a sensor’s ability to signal analarm state. This test requires that you use

Strona 24 - ELECTRIC HEATERS

3UNIT ARRANGEMENT AND ACCESSGeneralFig. 1 and Fig. 2 show general unit arrangement andaccess locations.INDOOR BLOWERACCESSCONTROL BOXCOMPRESSORS(D08-

Strona 25 - Limit Switches

30OPERATIONAL TEST HAZARDFailure to follow this caution may result in personneland authority concern.Changing the dirty sensor test operation will put

Strona 26 - SMOKE DETECTORS

31Table 13 – Detector IndicatorsCONTROL OR INDICATOR DESCRIPTIONMagnetic test/reset switch Resets the sensor when it is in the alarm or trouble state.

Strona 27 - Smoke Detector Locations

32AlarmPowerTest/resetswitchTroubleC07298Fig. 45 -- Controller AssemblyNOTE: All troubles are latched by the duct smokedetector. The trouble condition

Strona 28

33RTU--MP CONTROL SYSTEMThe RTU--MP controlle r, see Fig. 46, provides expandedstand--alone operation of the HVAC system plusconnec tion and control t

Strona 29 - Dirty Sensor Test

34C099015Fig. 47 -- RTU --MP System Control Wiring Diagram – 548J*04A — 548J*07A Units548J

Strona 30 - Remote Station Test

35C099025Fig. 48 -- RTU --MP System Control Wiring Diagram – 548J*08D & 548J*09D Units548J

Strona 31 - Indicators

36Table 14 – R TU--MP Controller Inputs and OutputsPOINT NAMEBACnet OBJECTNAMETYPE OF I/OCONNECTION PINNUMBERSINPUTSSpace Temperature Sensor sptsens A

Strona 32 - Test/reset

37Table 15 – Thermistor Resistance vs TemperatureValues for Space Temperature Sensor, Supply AirTemperature Sensor, and Outdoor Air TemperatureSensorT

Strona 33 - RTU--MP CONTROL SYSTEM

38SENSENJ20-1J20-2C08460Fig. 52 -- RTU --MP T--55 Sensor ConnectionsConnect T--56 -- See Fig. 53 for T--56 internalconnec tions. Instal l a jumpe r be

Strona 34

39Differential Enthalpy Control — Differential enthalpycontrol is provided by sensing and comparing the outsideair and return air e nthalpy conditions

Strona 35

4Outside Air HoodOutside air hood inle t screens are permanentaluminum--mesh type filters. Check these for cleanliness.Remove the screens when cleanin

Strona 36

40Outdoor Air Quality Sensor (PNO 33ZCSENCO2 plusweathe rproof enclosure) — The outdoor air CO2sensor isdesigned to monitor carbon dioxide (CO2) level

Strona 37 - HOLE IN END PANEL (HIDDEN)

41on manufacturer. Protocols do not change the function ofa controller; just make the front end user different.The RTU--MP can be set to communicate o

Strona 38 - Cool Warm

42C07170Fig. 64 -- BACview6Handheld ConnectionsRTU --MP TroubleshootingCommunication LEDsThe L EDs on the RTU--MP (see Fig. 46) i ndicate if thecontro

Strona 39

43Table 17 – Troubleshooting AlarmsPOINT NAMEBACnetOBJECTNAMEACTION TAKEN BYCONTROLRESETMETHODPROBABLE CAUSESafety Chain Alarm safety_chainAlarm Gener

Strona 40 - Power Exhaust (output)

44AlarmsAlarms can be checked through the network and/or thelocal access. All the alarms are listed in Table 17 withname , objec t name, action taken

Strona 41 - Baud Rate Selections

45S Max Masters: Defines the highest MS/TP Master MACaddress on this MS/TP network. For example, if t here are3 master nodes on an MS/TP network, and

Strona 42 - RTU --MP Troubleshooting

46Table 18 – Manufacture DateWhen troubleshooting, you may need to know a control module’s manufacture date.Obtain the manufacture date froma...NotesM

Strona 43

47N21. Verify that the BAS and controller are both set tospeak the N2 protocol. The protocol of the controlleris set via SW3 (switches 3, 4, 5, and 6)

Strona 44 - BACnet MS/TP

48Economizer 2 Position DamperUnit Without Economizer or2 Position DamperC08631Fig. 68 -- EconoMi$er IV Wiring435286711011912PINKVIOLETBLACKBLUEYELLOW

Strona 45

49Table 21 – EconoMi$er IV Input/Output LogicINPUTS OUTPUTSDemand ControlVentilation (DCV)Enthalpy*Y1 Y2Compressor NTerminal†Outdoor ReturnStage1Stage

Strona 46

5460, 575-v Units208/230-v UnitsC09263Fig. 7 -- EMC Unit WiringECM Motor – The di rect--drive motor is an X13Electronically Commutated motor (ECM). An

Strona 47 - ECONOMIZER SYSTEMS

50SUPPLY AIRTEMPERATURESENSORMOUNTINGLOCATIONSUPPLY AIRTEMPERATURESENSORC06033Fig. 71 -- Supply Air Sensor LocationThe temperature sensor looks like a

Strona 48 - 2 Position Damper

510510152025300.13 0.20 0.22 0.25 0.30 0.35 0.40 0.45 0.50STATIC PRESSURE (in. wg)FLOW IN CUBIC FEET PER MINUTE (cfm)C06031Fig. 74 -- Outdoor--Air Dam

Strona 49 - EconoMi$er IV

52TR124 VacCOMTR24 Va cHOT12345EFEF1+_P1T1PTNEXH2V 10VEXHSetSet2V 10V2V 10VDCVDCVFreeCoolBCADSO+SR+SRSOAQ1AQDCVMinPosOpenMaxN1C06038Fig. 77 -- EconoMi

Strona 50

53To determine the minimum position setting, perform thefollowing procedure:1. Calculate the appropriate mixed air temperature usingthe following form

Strona 51 - HIGH LIMIT

54graph with the left side of the chart to determine that therange configuration for the CO2sensor should be 1800ppm. The EconoMi$er IV controller wil

Strona 52 - RANGE CONFIGURATION (ppm)

55EconoMi$e r IV PreparationThis procedure is used to prepare the EconoMi$er IV fortroubleshooting. No troubleshooting or testing is done byperforming

Strona 53

565. Return EconoMi$er IV settings and wiring to normalafte r completing troubleshooting.EconoMi$e r IV TroubleshootingCompletionThis procedure is use

Strona 54

57C09200Fig. 80 -- 50TCQ Typical Unit Wiring Diagram -- Control (D08, 208/230--3--60)548J

Strona 55

58PRE--START--UPPERSONAL INJURY HAZARDFailure to follow this warning could result in personalinjury or death.1. Follow recognized safety practices and

Strona 56 - WIRING DIAGRAMS

59Internal WiringCheck all electric al connections in unit control boxes.Tighten as required.Refrigerant Service PortsEac h unit system has two1/4” SA

Strona 57

6Table 2 – Motor Test VoltsUnit Voltage Motor Voltage Min---Max Volts208/230 230 190---250460 230 210---250575 460 420---5005. Apply a jumper at unit

Strona 58 - START--UP, GENERAL

60service test. Indoor fans a nd outdoor fans are controllednormally to maintain proper unit ope ration. All normalcooling alarms and alerts are funct

Strona 59 - START--UP, RTU--MP CONTROL

61InputsNOTE: For i nstallation of inputs and field installe daccessories, refer to the appropriate sections.Input 3This input is a discrete input and

Strona 60 - Configuration

62Economize rEconomize r ExistsThis point tells the controller if there is an economizerinstalled on the unit.Factory Default = NO if no economizerYES

Strona 61

63position. Compressor 2 contactor (C2) is energized;Compressor 2 starts and Circuit 2 operates in Coolingmode.When Cooling Stage 2 is satisfied, ther

Strona 62 - OPERATING SEQUENCE

64de--energized as the dampers close below the PE--Onsetpoint.Damper movement from full closed to full open (or viceversa) will take between 11/2and 2

Strona 63

65are restored and phase sequence is correct. If no 24-vcontrol power is available to the PMR, the red LED willbe off.RTU--MP Sequence of OperationThe

Strona 64 - Supplemental Controls

66look for a contact closure whenever the Supply Fan Rel ayis on. If it is not enabled then it will always be the samestate as the Supply Fan Relay. T

Strona 65 - RTU--MP Sequence of Operation

67the difference between the indoor air quality and anoptional outdoor air quality sensor. If the outdoor airquality is not present then a fixed value

Strona 66

68APPENDIX I. MODEL NUMBER SIGNIFICANCEMODEL NUMBER NOMENCLATURE1234567891011121314151617185 4 8 J P 0 6 A 0 0 0 A 0 B 0 A A --____________ ______ ___

Strona 67 - FASTENER TORQUE VALUES

69APPENDIX II. PHYSICAL DATAPhysical Data (Cooling) 3 -- 6 TONS548J*04A 548J*05A 548J*06A 548J*07ARefrigeration System#Circuits/#Comp./Type 1/1/Scroll

Strona 68 - Serial Number Format

7Adjustable--Pitch Pulley on MotorThe motor pulley is an adjustable--pitch type that allows aservicer to implement changes in the fan wheel speed toma

Strona 69 - APPENDIX II. PHYSICAL DATA

70APPENDIX II. PHYSICAL DATA (cont.)Physical Data (Cooling) 7.5 -- 8.5 TONS548J*08D 548J*09DRefrigeration System#Circuits/#Comp./Type 2/2/Scroll 2/2/S

Strona 70

71APPENDIX III. FAN PERFORMANCEGeneral Fan Performance Notes:1. Interpolation is permissible. Do not extrapolate.2. External static pressure is the st

Strona 71 - APPENDIX III. FAN PERFORMANCE

72APPENDIX III. FAN PERFORMANCETable 25 – 548J*04A ELECTRIC DRIVE, X13MOTOR, 3 TON HORIZONTAL SUPPLYSPEED(TORQUE)TAPCFM ESP BHP1900 0.70 0.31975 0.60

Strona 72

73APPENDIX III. FAN PERFORMANCE (cont.)Table 27 – 548J*05A ELECTRIC DRIVE, X13MOTOR, 4 TON HORIZONTAL SUPPLYSPEED(TORQUE)TAPCFM ESP BHP11200 0.75 0.48

Strona 73 - MOTOR, 4 TON VERTICAL SUPPLY

74APPENDIX III. FAN PERFORMANCE (cont.)Table 29 – 548J*06A ELECTRIC DRIVE, X13MOTOR, 5 TON HORIZONTAL SUPPLYSPEED(TORQUE)TAPCFM ESP BHP11500 1.19 0.74

Strona 74

75APPENDIX III. FAN PERFORMANCE (cont.)Table 31 – 548J*04A 3 TON HORIZONTAL SUPPLYCFMAVAILABLEEXTERNALSTATICPRESSURE(IN.WG)0.2 0.4 0.6 0.8 1.0RPM BHP

Strona 75

76APPENDIX III. FAN PERFORMANCE (cont.)Table 33 – 548J*05A 4 TON HORIZONTAL SUPPLYCFMAVAILABLEEXTERNALSTATICPRESSURE(IN.WG)0.2 0.4 0.6 0.8 1.0RPM BHP

Strona 76

77APPENDIX III. FAN PERFORMANCE (cont.)Table 35 – 548J*06A 5 TON HORIZONTAL SUPPLYCFMAVAILABLEEXTERNALSTATICPRESSURE(IN.WG)0.2 0.4 0.6 0.8 1.0RPM BHP

Strona 77

78APPENDIX III. FAN PERFORMANCE (cont.)Table 37 – 548J*07A 6 TON HORIZONTAL SUPPLYCFMAVAILABLEEXTERNALSTATICPRESSURE(IN.WG)0.2 0.4 0.6 0.8 1.0RPM BHP

Strona 78

79APPENDIX III. FAN PERFORMANCE (cont.)Table 39 – 548J*08D 7.5 TON HORIZONTAL SUPPLYCFMAVAILABLEEXTERNALSTATICPRESSURE(IN.WG)0.2 0.4 0.6 0.8 1.0RPM BH

Strona 79

8HEAT PUMP REFRIGERATIONSYSTEMUNIT OPERATION AND SAFETY HAZARDFailure to follow this warning c ould cause personalinjury, death and/or equipment damag

Strona 80

80APPENDIX III. FAN PERFORMANCE (cont.)Table 41 – 548J*09D 8.5 TON HORIZONTAL SUPPLYCFMAVAILABLEEXTERNALSTATICPRESSURE(IN.WG)0.2 0.4 0.6 0.8 1.0RPM BH

Strona 81 - Table 43 – PULLEY ADJUSTMENT

81APPENDIX III. FAN PERFORMANCE (cont.)Table 43 – PULLEY ADJUSTMENTUnit Motor/Drive ComboMotor Pulley turns open0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5043phas

Strona 82

82APPENDIX IV. ELECTRICAL INFORMATIONTable 44 – 548J*04A 1--Stage Cooling 3 TONSV--Ph--HzVOLTAGERANGECOMP (ea) OFM (ea) IFMMIN MAX RLA LRA W ATTS FLA

Strona 83

83APPENDIX IV. ELECTRICAL INFORMATION (cont.)Table 47 – 548J*07A 1--Stage Cooling 6 TONSV --- P h --- H zVOLTAGERANGECOMP (ea) OFM (ea) IFMRLA LRA WAT

Strona 84

84APPENDIX IV. ELECTRICAL INFORMATION (cont.)Table 50 – Unit Wire/MOCP Sizing DataUNITN O M . V --- P H --- H ZIFMTYPEELECTRIC HEATER NO C.O. or UNPWR

Strona 85

85APPENDIX IV. ELECTRICAL INFORMATION (cont.)Table 50 — Unit Wire/MOCP Sizing Data (cont)UNITN O M . V --- P H --- H ZIFMTYPEELECTRIC HEATER w/ PWRD C

Strona 86

86APPENDIX IV. ELECTRICAL INFORMATION (cont.)Table 50 — Unit Wire/MOCP Sizing Data (cont)UNITN O M . V --- P H --- H ZIFMTYPEELECTRIC HEATER NO C.O. o

Strona 87

87APPENDIX IV. ELECTRICAL INFORMATION (cont.)Table 50 — Unit Wire/MOCP Sizing Data (cont)UNITN O M . V --- P H --- H ZIFMTYPEELECTRIC HEATER w/ PWRD C

Strona 88

88APPENDIX IV. ELECTRICAL INFORMATION (cont.)Table 50 — Unit Wire/MOCP Sizing Data (cont)UNITN O M . V --- P H --- H ZIFMTYPEELECTRIC HEATER NO C.O. o

Strona 89

89APPENDIX IV. ELECTRICAL INFORMATION (cont.)Table 50 — Unit Wire/MOCP Sizing Data (cont)UNITN O M . V --- P H --- H ZIFMTYPEELECTRIC HEATER w/ PWRD C

Strona 90

9OUTDOORCOILC09219Fig. 11 -- Cleaning Condenser Coil (Size 04--07 shown)C08206Fig. 12 -- Propping Up Top Panel4. For Sizes 04--07: Remove screws secur

Strona 91

90APPENDIX IV. ELECTRICAL INFORMATION (cont.)Table 50 — Unit Wire/MOCP Sizing Data (cont)UNITN O M . V --- P H --- H ZIFMTYPEELECTRIC HEATER NO C.O. o

Strona 92

91APPENDIX IV. ELECTRICAL INFORMATION (cont.)Table 50 — Unit Wire/MOCP Sizing Data (cont)UNITN O M . V --- P H --- H ZIFMTYPEELECTRIC HEATER w/ PWRD C

Strona 93

92APPENDIX IV. ELECTRICAL INFORMATION (cont.)Table 50 — Unit Wire/MOCP Sizing Data (cont)UNITN O M . V --- P H --- H ZIFMTYPEELECTRIC HEATER NO C.O. o

Strona 94

93APPENDIX IV. ELECTRICAL INFORMATION (cont.)Table 50 — Unit Wire/MOCP Sizing Data (cont)UNITN O M . V --- P H --- H ZIFMTYPEELECTRIC HEATER w/PWRD C.

Strona 95

94APPENDIX IV. ELECTRICAL INFORMATION (cont.)Table 50 — Unit Wire/MOCP Sizing Data (cont)UNITN O M . V --- P H --- H ZIFMTYPEELECTRIC HEATER NO C.O. o

Strona 96 - AC = 226 v

95APPENDIX IV. ELECTRICAL INFORMATION (cont.)Table 50 — Unit Wire/MOCP Sizing Data (cont)UNITN O M . V --- P H --- H ZIFMTYPEELECTRIC HEATER w/PWRD C.

Strona 97 - Location

96Legend and Notes for Table 50LEGEND:CO --- Convenient outletDISC --- DisconnectFLA --- Full load ampsIFM --- Indoor fan motorLRA --- Locked rotor am

Strona 98

97APPENDIX VI. MOTORMASTER SENSOR LOCATIONSSensorLocationC09191Fig. 81 -- 548J*04A Outdoor CircuitingSensorLocationC09192Fig. 82 -- 548J*05A Outdoor C

Strona 99 - START-UP CHECKLIST

98APPENDIX VI. (cont) MOTORMASTER SENSOR LOCATIONSSensorLocationC09195Fig. 85 -- 548J*08D/09D Outdoor CircuitingManufacturer r es er ves the right to

Strona 100 - Catalog No. SM548J---01

99START-UP CHECKLIST(Remove and Store in Job File)I. PRELIMINARY INFORMATIONMODEL NO.: SERIAL NO.:DATE: TECHNICIAN:II. PRE-STAR T-UP (insert checkmark

Komentarze do niniejszej Instrukcji

Brak uwag