Bryant 580J*04--12 Instrukcja Instalacji Strona 23

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 22
23
value becomes the final minimum damper position of the
economizer output.
If the IAQ minimum position calculated by the control is
greater than the DCV Max Vent Damper Pos configured,
then it will be clamped to the configured value.
Dehumidification
The RTU Open will provide occupied and unoccupied
dehumidification only on units that are equipped with the
Perfect Humidity
t
option from the factory. This function
requires a space relative humidity sensor or a humidistat
for control. The space relative humidity senor can be
installed and configured as one of the two analog input
channels (inputs 1 or 2 on J4), or a humidistat can be
installed and configured as switch input 9 on J5. When
using a relative humidity sensor to control
dehumidification, occupied or unoccupied dehumidification
setpoints are use accordingly. When using a humidistat,
setpoints are not used and the dehumidification call comes
when the humidistat indicates high humidity.
When the indoor relative humidity becomes greater than the
dehumidification setpoint (or switches from low to high), a
demand for dehumidification demand is identified.
Compressor state is monitored and time guards are honored.
If a compressor was just turned off prior to the dehum call
the dehumidification output will be delayed the 5 minute
minimum off time of the compressor. When ok to
dehumidify, the dehumidification output (J11--7, 8) will be
energized. This will bring on the supply fan (at high fan
speed if Fan Control is set to “Two Speed” or “Variable
Speed”), all compressors, and the dehumidification relay
placing the unit in Hot Gas Reheat dehumidification mode.
If dehumidification is called for during cooling or cooling is
called for during dehumidification, the unit will run in
Subcooling dehumidification mode. Individual unit circuits
can be in different dehumidification modes based on the
demand. Refer to the base units operation for additional
information.
NOTE: There is a fixed 5% hysteresis that the indoor
relative humidity must drop below the active setpoint to
end the dehumidification mode and de--energize the
dehumidification output. The output will also de--energize
if the fan relay is de--energized.
Demand Limit
If the RTU Open receives a level 1 (one degree offset), 2
(two degree offset), or a 3 (4 degree offset) to the BACnet
demand limit variable, the controller will outwardly expand
the heating and cooling setpoints by the configured demand
limit setpoint value and remain in effect until the BACnet
demand limit variable receives a 0 value.
Unoccupied Free Cooling
When the unit is equipped with an economizer, the control
can run a night time free cooling (NTFC) mode called
Unocc Free Cooling. In this mode the damper is utilized
to bring in outdoor air for free cooling during unoccupied
periods. The following conditions must be true for
unoccupied free cooling to operate:
S Unocc Free Cool Enable set to Enable
S The system is unoccupied
S The outside air temperature is below the Economizer
High OAT Lockout Temp
S The outside air temperature is less than the space
temperature
S Enthalpy (if enabled) is Low
When the RTU Open schedule is unoccupied and the
space temperature rises at least 1 degree above the
Occupied Cooling Setpoint, the supply fan starts. The
economizer damper opens as necessary to cool the space.
The RTU Open continues to operate in this mode until the
space is satisfied or the outside air conditions are no
longer suitable for free cooling.
Optimal Start
The RTU Open may utilize Optimal Start, which adjusts
the effective setpoints to achieve the occupied setpoints
by the time scheduled occupancy begins. The algorithm
works by moving the unoccupied setpoints toward the
occupied setpoints. The rate at which the setpoints move
is based on the outside air temperature, design
temperatures, and capacities. The Optimal Start recovery
period may begin as early as 4 hours prior to occupancy.
To disable Optimal Start, set the optimal start type to
None. The following conditions must be true for optimal
start to operate:
S Under SETPOINT, Optimal Start Value must be set
greater than zero
S The Optimal Start type must not be None
S The system is unoccupied
S The RTU Open has a valid outside air temperature
S The RTU Open is running occupancy based on a local
occupancy schedule, where next time occupied is known.
Fire Shutdown
Fire Shutdown may be configured on Binary Input 5. A
typical application involves a smoke detector or fire
shutdown contact, which, when active, immediately shuts
down equipment operation.
Compressor Safety
Compressor Safety may be configured on Binary Input 3.
This feedback can be provided by a Compressor
Lock--Out (CLO) device or current switch when field
installed. A Compressor Safety Alarm indicates that the
equipment requires attention. Cooling, heating, and supply
fan outputs are not interrupted. Normal operation resumes
when the compressor safety circuit is de--energized.
Fan Status
Fan Status may be configured on any unused binary input
channel. A typical application would be an airflow switch,
current sensing relay, or other device that provides a supply
fan running verification. Enabling this function displays the
supply fan’s status on the equipment graphic. If the
controller loses fan status during operation, heating and
cooling are disabled, the economizer damper (if available) is
closed, and an alarm for loss of status is indicated. If the fan
status is on when the controller is commanding the fan off,
the unit remains in the off state. An alarm is generated
indicating that the fan is running when it should be off.
TS---5580J---02
Przeglądanie stron 22
1 2 ... 18 19 20 21 22 23 24 25 26 27 28 ... 47 48

Komentarze do niniejszej Instrukcji

Brak uwag