Page 19
Features
• Anti-short cycle protection
• High and Low pressure cutouts
• Water Coil freeze protection
• Air Coil freeze protection
• Random Start
• Unit Performance Sentinel
• Over/Under Voltage protection
• Diagnostic LED
• Reset Lockout at unit or disconnect
• Intelligent Reset
• Condensate Overfl ow sensor
• Test Mode
• Electric Heat Outputs
• Accessory Water Valve Connection
• Optional LonWorks Control
Field Selectable Inputs
Test Mode - Test Mode allows the service personnel to
check the operation of the control in a timely manner. By
momentarily shorting the test terminals, the CXM control
enters a 20 minute Test Mode period in which all time
delays are sped up 15 times. Upon entering Test Mode, the
Status LED will fl ash a code representing the last fault.
For Diagnostic ease at the thermostat, the alarm relay will
also cycle during test mode. The Alarm relay will cycle
on and off similar to the status LED to indicate a code
representing the last fault, at the thermostat. Test mode can
be exited by shorting the test terminals for 3 seconds.
CXM Control Description
Retry Mode - If the control is attempting a retry of a fault,
the status LED will slow fl ash (slow fl ash = one fl ash every
2 seconds) to indicate the control is in process of retrying.
NOTE: In the following fi eld confi guration options,
jumper wires should be clipped ONLY when power is
removed from the CXM control.
Water Coil Freeze Protection Limit Setting - Jumper
2 (JW3-F12 Low Temp) provides fi eld selection of
temperature limit setting for FP1 to be 30°F or 10°F.
Not Clipped = 30°F. Clipped = 10°F.
Air Coil Freeze Protection Limit Setting - Jumper
3 (JW2-FP2 Low Temp) provides fi eld selection of
temperature limit setting for FP2 to be 30°F or 10°F.
Not Clipped = 30°F. Clipped = 10°F.
Alarm Relay Setting - Jumper 1 (JW1-AL2 Dry) provides
fi eld selection of Alarm Relay terminal AL2 to be
jumpered to 24Vac or to be dry (no connection).
Not Clipped = AL2 connected to R. Clipped = AL2 dry
contacts (no connection).
DIP Switches
Unit Performance Sentinel Disable - Dip Switch 1
provides fi eld selection to disable the UPS feature:
On = Enabled. Off = Disabled.
Stage 2 - Dip Switch 2 provides selection of whether
compressor has an on delay. If set to stage 2, the
compressor will have a 3 second delay before energizing.
Also, if set for stage 2, the alarm relay will NOT cycle
during test mode:
On = Stage 1. Off = Stage 2.
Table 7. LED & Alarm Relay Operations
Special Notes and Examples:
-Slow Flash = 1 fl ash every 2 seconds
-Fast Flash = 2 fl ashes every 1 second
-Flash code 2 = 2 quick fl ashes, 10 sec.
pause, 2 quick fl ashes, 10 sec. pause, etc.
Description of Operation LED Alarm Relay
Normal Mode On Open
Normal Mode with UPS Warning On Cycle (closed 5 sec., Open 25 sec.)
CXM is non-functional Off Open
Fault Retry Slow Flash Open
Lockout Fast Flash Closed
Over/Under Voltage Shutdown Slow Flash Open (Closed after 15 minutes)
Test Mode - No fault in memory Flashing Code 1 Cycling Code 1
Test Mode - HP Fault in memory Flashing Code 2 Cycling Code 2
Test Mode - LP Fault in memory Flashing Code 3 Cycling Code 3
Test Mode - FP1 Fault in memory Flashing Code 4 Cycling Code 4
Test Mode - FP2 Fault in memory Flashing Code 5 Cycling Code 5
Test Mode - CO Fault in memory Flashing Code 6 Cycling Code 6
Test Mode - Over/Under
shutdown in memory
Flashing Code 7 Cycling Code 7
Test Mode - UPS in memory Flashing Code 8 Cycling Code 8