Antifreeze may be added before, during or after the
ushing procedure. However, depending upon which time
is chosen, antifreeze could be wasted when emptying the
ush cart tank. See antifreeze section for more details.
Loop static pressure will uctuate with the seasons.
Pressures will be higher in the winter months than during
the cooling season. This uctuation is normal and should
be considered when charging the system initially. Run the
unit in either heating or cooling for a number of minutes
to condition the loop to a homogenous temperature. This
is a good time for tool cleanup, piping insulation etc. Then
nal ush and pressurize the loop to a static pressure of
40-50 psi (winter) 15-20 psi (summer).
After pressurization, be sure to remove the plug in the end
of the Grundfos loop pump motor(s) to allow trapped air
to be discharged and to insure the motor housing has been
ooded. This is not required for Taco circulators. Insure
the loop ow center provides adequate ow through the
unit by checking pressure drop across the heat exchanger
and comparing it to the gures shown in Table 11.
Antifreeze
In areas where minimum entering loop temperatures
drop below 40°F or where piping will be routed through
areas subject to freezing, anti-freeze is needed. Alcohols
and glycols are commonly used as antifreezes, however
your local territory manager should be consulted for the
antifreeze best suited to your area. Freeze protection
should be maintained to 15°F below the lowest expected
entering loop temperature. For example, if 30°F is
the minimum expected entering loop temperature,
the leaving loop temperature would be 25-22°F and
freeze protection should be at 15°F (30°F-15°F=15°F).
All alcohols should be premixed and pumped from
a reservoir outside of the building when possible or
introduced under water level to prevent fuming. Initially
calculate the total volume of uid in the piping system
using Table 2. Then use the percentage by volume shown
in Table 3 for the amount of antifreeze. Antifreeze
concentration should be checked from a well mixed
sample using a hydrometer to measure speci c gravity
See Flow Controller IOM for more information.
Freeze Protection Setting
CXM or DXM Control:
When an antifreeze is selected, the FP1 jumper (JW3)
should be clipped to select the low temperature
(Antifreeze 10°F) setpoint to avoid nuisance faults. See
Freeze Protection Selection. Shut off valves should be
included in case of servicing. Boiler drains or other valves
should be "teeʼd" in the line to allow acid ushing of just
the heat exchanger. Pressure temperature plugs should be
used so that ow and temperature can be measured. The
water freezestat should be wired. Piping materials should
be limited to PVC SCH80 or copper. Note: Due to the
pressure and temperature extremes, PVC SCH40 is
not recommended.
Figure 10. Typical Closed Loop System.